Building and Construction 892 practice questions

Journeyman Electrician Practice Test

Practise for the Journeyman Electrician with 892 exam-style questions, an explanation for every answer and stats that show what to study next.

Every answer explainedAn explanation for every answer as you practise.
Progress by topicSee which parts of the Journeyman Electrician need more work.
Short or full setsTen-minute sessions or longer timed practice.

What is the journeyman electrician exam?

There is no single national journeyman electrician exam. Each state or local authority sets its own license name, exam, fee and National Electrical Code (NEC) edition, so the numbers that apply to you are the ones in your own candidate bulletin. In the official documents checked on November 7, 2026, exams ran from 70 to 100 scored questions and 180 to 330 minutes, and current bulletins set the pass mark at 70%.

Start by finding your licensing agency. The Bureau of Labor Statistics says most states require a license and that the rules differ by state. The license name may differ too: look for General Electrician in California, Journeyman Wireman in Colorado, Journeyperson Electrician in Maryland, Class A journeyworker in Minnesota and 01 General Journey Level in Washington.

The NASCLA Accredited Examination for Journeyman Electricians is the closest thing to a multi-state exam, but it is not a national license. NASCLA's pages list this exam for Alabama, Idaho, Kentucky and Nebraska. That is not a full list, so confirm with your agency that it accepts the score before you apply.

What are the journeyman electrician requirements?

Your agency decides, and most routes rest on documented work hours. These examples are not legal advice, so check your agency's current rules before you rely on them:

  • Texas: 7,000 hours under a Texas master electrician to sit the exam, 8,000 hours for the license.
  • California: 8,000 hours on the job for General Electrician.
  • Washington: 8,000 hours plus 96 classroom hours, with specialty hours capped at 4,000.
  • NASCLA: apply to NASCLA first. A state license application is separate.

Format by state

These are examples from official documents, not a full list of states. Bulletins change, so recheck them before you register.

Exam Scored questions Time To pass Exam fee NEC edition Book rule
Texas 56 knowledge, 24 calculations 130 + 110 min 70% on each $78 2026 Own soft-bound NEC, no handbook
Minnesota 80 330 min 70% $50 2026 NEC supplied
California (General Electrician) 100 270 min 70% $100 (2019 fee page) 2023 Supplied on screen, no own materials
Colorado 90 240 min 70% $78 2026 NEC and formula page supplied
Iowa 80 180 min 70% $87 2023 NEC or NEC Handbook
Virginia 70, including 10 on state regulations 210 min 49 correct $100 2020 Own book, no study guides
Washington (01 General) 60 on NEC and theory, 17 on state codes 180 + 60 min 70% on each Billed by exam hours, see bulletin 2020 Own books, state law copies in a binder
NASCLA 100 300 min 70 Not in bulletin 2020 or 2023 NEC or Handbook, plus listed references

Colorado allows the 2023 edition on request until December 1, 2026. Some exams also add non-scored questions, and Colorado and Iowa add 30 minutes for them.

Which NEC edition should you study?

Study the edition named in your bulletin, even if it differs from the book you own. Texas lets you bring any soft-bound edition, but its questions follow the edition the state adopted. NFPA keeps an NEC enforcement map you can use as a starting point.

If your exam uses the 2026 edition, check your old notes. EC&M, a trade magazine, reports that load calculations moved from Article 220 to Article 120. It also reports a dwelling general lighting load of 2 VA per square foot for feeders and services, down from 3 VA. The same article says 3 VA still applies when you work out the minimum number of branch circuits. Notes built on the older article numbers and load figure can cost you points.

The free questions on this page assume the 2023 NEC and name it in each code question. Section numbers and some rules differ in other editions, so check each answer against the book your exam uses. Safety questions follow federal OSHA, and your state plan may differ.

What is on the journeyman electrician test?

Mostly NEC application, but the official weights differ by exam, so the same study plan will not fit every state.

  • Wiring and protection plus wiring methods make up 34% of NASCLA, 44% of Iowa and about 46% of Maryland.
  • Theory is about 29% of Maryland's 2024 outline. Iowa lists no separate theory or safety area.
  • Calculations are 24 of 80 scored questions in Texas (30%) and 9 of 90 in Colorado (10%).
  • California groups its outline by task: Installation is 66%, Determination of Electrical System Requirements 22%, and Safety and Maintenance and Repair 6% each.
  • Virginia sets aside 10 of its 70 questions for state regulations, and Washington 17 of its 77 for RCW 19.28 and WAC 296-46B. National prep material may skip those.

How to study for the journeyman electrician test

Copy the weights from your own bulletin, then give each area a share of your hours that matches its weight. None of the documents checked says how many hours you need. The table uses the NASCLA outline and an example of 50 hours, so scale it to your own time.

NASCLA area Questions of 100 Example hours of 50
Wiring and Protection 18 9
Wiring Methods and Materials 16 8
General Code Requirements 15 7.5
Electrical Theory and Principles 10 5
Equipment for General Use 10 5
Basic Electrical Safety 8 4
Special Occupancies and Special Equipment 8 4
Testing and Troubleshooting 7 3.5
Interpreting Plans and Specifications 6 3
Special Conditions and Communication Systems 2 1

Then adjust for how your exam works:

  1. Work out your minutes per question. Counting non-scored items, NASCLA allows about 2.7, Virginia about 2.6 to 3 and Minnesota about 4. Texas allows about 2.2 on knowledge questions and about 4.2 on calculations. Time your practice sets to match.
  2. Practice with the same book you will use. If the center supplies an untabbed NEC, as Minnesota does, stop relying on your own tabs and highlights.
  3. Know your exam's assumptions. The Texas bulletin says to ignore code exceptions and optional calculation methods unless the question directs otherwise, and to assume copper unless noted. That instruction applies only to Texas.
  4. Give calculations their own sessions if your exam counts them heavily, as Texas does.
  5. Add a separate block for state law if your bulletin lists it.

Free journeyman electrician practice test and next steps

The 20 free questions on this page were written for study and are not real exam questions. They follow the NASCLA weights as a study mix, not the outline of any state's exam. After rounding, Special Conditions and Communication Systems gets no question in the set. Five of the 20 are calculations, and you get an explanation for every answer.

Your next steps:

  1. Download your agency's current bulletin and note the edition, book rule and weights.
  2. Confirm your hours and application route with the agency.
  3. Try the free set, then put more time on your weakest high-weight areas.

The VirtuePrep app has 892 Journeyman Electrician questions if you want more practice, and you can see other tests on the exams page.

20 free Journeyman Electrician practice questions

Answer each one yourself, then open the answer. No account needed. These are study questions, not real exam questions.

  1. You are copying circuit descriptions from a panel schedule to the directory of a new enclosed panelboard in a dental office. The schedule shows circuit 7 feeding the receptacles on the north wall of Room 104, which Dr. Patel uses now. Under the 2023 NEC, which directory entry is best?

    1. Dr. Patel's room outlets
    2. Misc. loads, as needed
    3. RCP-N, with no key on the panel
    4. Receptacles, Room 104 north wall
    Show answer

    Answer: D. The 2023 NEC directory rule in 408.4(A) calls for each circuit to be described clearly and specifically, in enough detail to avoid mixing it up with another circuit. Room 104 and the wall location will still mean something after staff move. A person's name depends on who occupies the room, and abbreviations need an explanation when used.

    Source: 2023 NEC 408.4(A), as shown in NFPA's public input report for the 2026 cycle, Panel 10

  2. Working under federal OSHA general industry rules, you open the disconnect for a 480 V conveyor motor and put your lock and tag on it. What must happen before anyone treats the circuit as de-energized?

    1. Enter the handle position and the time in the shift job log
    2. Have a coworker confirm the lock and tag on the disconnect
    3. Have a qualified person try the controls and test for voltage
    4. Check that the run indicator on the motor starter has gone out
    Show answer

    Answer: C. 29 CFR 1910.333(b)(2)(iv) requires a qualified person to operate the controls or otherwise verify the equipment cannot restart, then use test equipment to confirm the parts are de-energized. That test also has to catch induced voltage or unrelated backfeed. A lock and tag alone do not prove the circuit is dead. This is a federal OSHA rule, so no NEC edition applies.

    Source: 29 CFR 1910.333, federal OSHA electrical work practices

  3. On a construction site covered by federal OSHA, crews plug tools into 120 V, single-phase, 20 A receptacles that are not part of the building's permanent wiring. No small portable generator is involved. Which approach meets 29 CFR 1926.404(b)(1)?

    1. GFCI protection, or a written assured equipment grounding conductor program
    2. Grounding-type plugs on every cord, with a weekly visual check by the foreman
    3. A dedicated 20 A breaker ahead of each receptacle, with a yearly test by an electrician
    4. Double-insulated tools only, with no other protection on the temporary receptacles
    Show answer

    Answer: A. 29 CFR 1926.404(b)(1) gives the employer two routes: approved GFCIs on those receptacles, or an assured equipment grounding conductor program. The program needs a written description, a competent person, daily visual checks and tests at set intervals with records. State OSHA plans and the code your area adopted can be stricter, so check them on a real job. This is a federal OSHA rule, so no NEC edition applies.

    Source: 29 CFR 1926.404, federal OSHA construction wiring design and protection

  4. A 120 V source supplies a heater drawing 16 A. Each of the two circuit conductors has 0.20 ohm of resistance. If the source holds 120 V, about how many volts reach the heater? This is a theory question, so no NEC edition applies.

    1. 120.0 V
    2. 116.8 V
    3. 113.6 V
    4. 107.2 V
    Show answer

    Answer: C. Current flows out and back, so the total conductor resistance is 0.40 ohm. Ohm's law gives a drop of 16 A x 0.40 ohm = 6.4 V, and 120 V minus 6.4 V leaves 113.6 V at the heater.

    Source: DOE Fundamentals Handbook, Electrical Science, Volume 1 (DOE-HDBK-1011/1-92)

  5. Two identical resistance elements are wired in series across 240 V, and one has burned open. A qualified person with a properly rated meter reads across each element with the supply on. What should the readings be? This is a theory question, so no NEC edition applies.

    1. About 120 V across each element
    2. About 0 V across the open one, 240 V across the good one
    3. About 0 V across both elements
    4. About 240 V across the open one, 0 V across the good one
    Show answer

    Answer: D. An open in a series circuit stops the current, and with no current the good element has no IR drop. By Kirchhoff's voltage law, the drops around the loop still equal the source, so nearly all 240 V appears across the break in the open element. That reading points you to the failed part.

    Source: U.S. Navy Electricity and Electronics Training Series (NEETS), Book 1, Direct Current chapter, section on open circuits, online copy at tpub.com

  6. A branch-circuit breaker feeding a motor trips. The circuit design and the breaker's response point to a fault, not an overload. Under federal OSHA rules, what is required before the circuit is manually re-energized?

    1. Reset it once to see whether it holds under normal motor load
    2. Replace it with a new breaker of equal rating, then restart
    3. Determine that the equipment and circuit can be safely energized
    4. Raise the trip setting one step so that the motor can restart
    Show answer

    Answer: C. 29 CFR 1910.334(b)(2) bars manually re-energizing until someone has determined the equipment and circuit can be safely energized. Repeated manual reclosing, or replacing fuses to re-energize, is prohibited. A note to the rule drops the examination only where the design and devices show the trip came from an overload, and this stem points to a fault. This is a federal OSHA rule, so no NEC edition applies.

    Source: 29 CFR 1910.334, federal OSHA use of equipment

  7. A new 480Y/277 V enclosed panelboard is installed so that a poured concrete wall is directly across the aisle. No other electrical equipment is nearby. Under the 2023 NEC, what is the minimum clear depth of working space in front of the panel?

    1. 3 ft
    2. 3 ft 6 in.
    3. 4 ft
    4. 5 ft
    Show answer

    Answer: B. The voltage to ground is 277 V, which falls in the 151 to 600 V row of Table 110.26(A)(1). A concrete wall counts as grounded, so this is Condition 2, and the table gives 3 ft 6 in. Measure from the enclosure front, because the live parts are enclosed.

    Source: 2023 NEC 110.26(A)(1), as shown in NFPA's public input report for the 2026 cycle, Panel 1

  8. A 60 A circuit uses 6 AWG copper THHN conductors, with three or fewer current-carrying conductors in the raceway at 30°C ambient. The breaker and equipment terminals are listed and marked for 75°C. Under the 2023 NEC, what ampacity can you use for the conductor at those terminations?

    1. 55 A
    2. 60 A
    3. 65 A
    4. 75 A
    Show answer

    Answer: C. THHN has a 90°C rating, but 110.14(C)(1) ties the usable ampacity to the temperature rating of the terminals. In Table 310.16, 6 AWG copper is 55 A at 60°C, 65 A at 75°C and 75 A at 90°C. The 75°C terminals set the figure at 65 A.

    Source: 2023 NEC 110.14(C)(1) in NFPA's public input report for the 2026 cycle, Panel 1. Table 310.16 is reprinted in the Panel 6 report

  9. A breaker's label gives a torque value for its lugs. The crew member landing a 4 AWG conductor has no torque tool in the van. Under the 2023 NEC, what does the code call for?

    1. Use an approved means, such as a torque tool, to reach the marked value
    2. Tighten by feel, then mark each lug after a pull test on the conductor
    3. Use a torque tool only where the inspector asks to see a record
    4. Use a torque tool only where the conductor is larger than 1/0 AWG
    Show answer

    Answer: A. Section 110.14(D) makes the indicated torque value a requirement and calls for an approved means of achieving it. An informational note gives torque tools, shear bolts and breakaway devices with visual indicators as examples. The rule sets no conductor size threshold, and it applies whether or not an inspector asks.

    Source: 2023 NEC 110.14(D), as shown in NFPA's public input report for the 2026 cycle, Panel 1

  10. A feeder supplies 64 A of continuous load and 30 A of noncontinuous load. Its overcurrent device is not part of an assembly listed for 100 percent operation. Under the 2023 NEC, what is the minimum overcurrent device rating?

    1. 94 A
    2. 110 A
    3. 118 A
    4. 125 A
    Show answer

    Answer: B. Section 215.3 sets the minimum at 125 percent of the continuous load plus all of the noncontinuous load. That is 30 A + (64 A x 1.25) = 30 A + 80 A = 110 A. Only the continuous part gets the 125 percent factor.

    Source: 2023 NEC 215.3, as shown in NFPA's public input report for the 2026 cycle, Panel 10

  11. Six current-carrying 10 AWG copper THHN conductors share one raceway at 30°C ambient, and all terminals are marked for 75°C. No special rule for motors or taps applies. Under the 2023 NEC, what is the largest breaker that may protect these conductors?

    1. 25 A
    2. 30 A
    3. 35 A
    4. 40 A
    Show answer

    Answer: B. Start at the 90°C column: 40 A. Table 310.15(C)(1) gives 80 percent for four to six conductors, so the adjusted ampacity is 32 A, which is under the 35 A shown for the 75°C terminals. Section 240.4(D) then limits 10 AWG copper to 30 A after those adjustments, so you cannot go up to a 35 A breaker.

    Source: 2023 NEC 240.4(D) in NFPA's public input report for the 2026 cycle, Panel 10. Section 310.15(C)(1) and Table 310.16 are reprinted in the Panel 6 report

  12. A new fitness center needs a panelboard with standard branch-circuit breakers. The plans show it on a wall inside a locker room with showers, well away from the shower stalls. Under the 2023 NEC, what should you do about the location?

    1. Keep it there, in an enclosure rated for wet locations
    2. Move it to an electrical room off the main corridor
    3. Keep it there, behind a door only staff can open
    4. Move it to the adjoining restroom, which has a toilet and sink
    Show answer

    Answer: B. Section 240.24(E) keeps overcurrent devices, apart from supplementary protection, out of bathrooms, showering facilities and locker rooms that have showers. Branch-circuit breakers are not supplementary protection, so this panelboard has to go elsewhere. An enclosure rating, a lock or distance from the stalls does not change the rule, and a restroom with a toilet and sink counts as a bathroom.

    Source: 2023 NEC 240.24(E), as shown in NFPA's public input report for the 2026 cycle, Panel 10

  13. A subpanel in the same building as the service is fed by a feeder with an equipment grounding conductor. You find its neutrals and grounds on one bar, with the bar bonded to the enclosure. Under the 2023 NEC, what is the correct fix?

    1. Drive a ground rod at the subpanel and keep the bar bonded to it
    2. Remove the feeder's grounding conductor and keep the bar bonded
    3. Add a second bonding jumper from the shared bar to the enclosure
    4. Isolate neutrals from the enclosure and move grounds to a bonded bar
    Show answer

    Answer: D. Section 250.24(B) in the 2023 NEC bars connecting the grounded conductor to equipment grounding conductors or normally non-current-carrying metal on the load side of the service disconnect, unless the article permits it. Section 408.40 calls for the equipment grounds to land on a terminal bar bonded to the cabinet. A bond between neutral and enclosure here would put neutral current on metal parts and grounding paths. Separate buildings have their own rules, which is why this question says same building.

    Source: 2023 NEC 250.24(B) in NFPA's public input report for the 2026 cycle, Panel 5. Section 408.40 is reprinted in the Panel 10 report

  14. A sheet metal pull box on a 480 V feeder run has no listing for reduced dimensions. Raceways with insulated 4 AWG or larger conductors enter its left wall in two rows, and every conductor turns 90 degrees to leave through the bottom wall. The upper row holds trade sizes 3 1/2 and 1. The lower row holds trade sizes 3, 3 and 2. Using trade size as the raceway diameter, what minimum left wall to right wall distance do these entries require under the 2023 NEC?

    1. 21 in.
    2. 22 in.
    3. 23 in.
    4. 30 in.
    Show answer

    Answer: C. Section 314.28(A)(2) in the 2023 NEC sizes an angle pull one row at a time: six times the largest trade size in that row, plus the trade sizes of the others in it. The upper row gives (6 x 3 1/2 in.) + 1 in. = 22 in. The lower row gives (6 x 3 in.) + 3 in. + 2 in. = 23 in. The higher result governs, so the answer is 23 in., even though the largest raceway is in the upper row.

    Source: 2023 NEC 314.28(A)(2), as shown in NFPA's public input report for the 2026 cycle, Panel 8

  15. A straight EMT run leaves a junction box along a wall where framing allows a strap at any point. The first strap is 4 ft from the box, and the later straps are 8 ft apart. Under the 2023 NEC, what needs to change?

    1. Move the first strap to within 3 ft of the box
    2. Reduce the 8 ft strap spacing to 4 ft or less
    3. Move the first strap to within 12 in. of the box
    4. Nothing, because a first strap may sit up to 5 ft from the box
    Show answer

    Answer: A. Section 358.30(A) requires fastening at intervals up to 10 ft and within 3 ft of each box. The 8 ft spacing is fine. The 5 ft allowance applies to unbroken lengths only where structural members do not readily permit a closer strap, and this wall allows one.

    Source: 2023 NEC 358.30(A), as shown in NFPA's public input report for the 2026 cycle, Panel 8

  16. Nonmetallic-sheathed cable passes through a bored hole in a wood stud, and the edge of the hole ends up 1 in. from the stud face that will receive drywall. Under the 2023 NEC, what is the standard fix?

    1. Leave it, since 1 in. of wood is enough to stop drywall screws
    2. Cut a notch along the stud face and recess the cable into it
    3. Slide a short PVC sleeve over the cable at the bored hole
    4. Add a steel plate or bushing at least 1/16 in. thick
    Show answer

    Answer: D. Section 300.4(A)(1) sets a minimum of 1 1/4 in. from the edge of the hole to the edge of the member. Where that cannot be kept, a steel plate or bushing at least 1/16 in. thick must protect the cable from screws and nails. A listed and marked thinner plate with equal or better protection is also allowed.

    Source: 2023 NEC 300.4(A)(1), as shown in NFPA's public input report for the 2026 cycle, Panel 3

  17. A pump house feeder supplies only three continuous-duty 230 V, three-phase induction motors with normal speed and torque: 40 hp, 15 hp and 7.5 hp. Their nameplates read 98 A, 39 A and 20 A. Under the 2023 NEC, what is the minimum feeder conductor ampacity?

    1. 168 A
    2. 181.5 A
    3. 194 A
    4. 210 A
    Show answer

    Answer: C. Section 430.6(A)(1) sends you to the table, not the nameplate. The 230 V column of Table 430.250 gives 104 A, 42 A and 22 A. Section 430.24 then adds 125 percent of the largest motor to the others: (104 A x 1.25) + 42 A + 22 A = 130 A + 64 A = 194 A.

    Source: 2023 NEC 430.24, 430.6(A)(1) and Table 430.250, as shown in NFPA's public input report for the 2026 cycle, Panel 11

  18. You are replacing a two-wire receptacle in a private office in an older commercial building. The box has no equipment grounding conductor, and the tenant wants a three-slot receptacle. Under the 2023 NEC, which replacement is allowed?

    1. A GFCI-type receptacle marked "No Equipment Ground"
    2. A grounding-type receptacle with its ground screw jumped to neutral
    3. A grounding-type receptacle with no GFCI protection or marking
    4. A GFCI-type receptacle with a wire from its ground to downstream outlets
    Show answer

    Answer: A. Section 406.4(D)(2) allows a GFCI-type receptacle in this case, marked "No Equipment Ground" on the receptacle or cover plate. No wire may run from its grounding terminal to outlets it supplies. Jumping the ground screw to neutral could energize the metal frames of plugged-in equipment.

    Source: 2023 NEC 406.4(D)(2), as shown in NFPA's public input report for the 2026 cycle, Panel 18

  19. In a mixing room, volatile solvents stay in closed tanks and piping. Positive mechanical ventilation normally keeps ignitible vapor out of the room, and vapor could build up only if that ventilation fails. No Division 1 area adjoins the room. Under the 2023 NEC, how is this room classified?

    1. Class I, Division 2
    2. Class I, Division 1
    3. Class II, Division 2
    4. Class II, Division 1
    Show answer

    Answer: A. Solvent vapor is a Class I hazard, while Class II covers combustible dust. Section 500.5(B)(2) places a location in Division 2 where liquids stay confined in closed systems, or where ventilation normally prevents ignitible concentrations and failure could change that. Federal OSHA's definitions in 29 CFR 1910.399 describe it the same way.

    Source: 2023 NEC 500.5(B)(2), as shown in NFPA's public input report for the 2026 cycle, Panel 14

  20. A garage needs a 240 V, 40 A outlet for electric vehicle supply equipment. To save a breaker space, the installer wants to feed it from the same branch circuit as a 240 V air compressor. No energy management system is involved. Under the 2023 NEC, what is required?

    1. A shared circuit, if the two loads stay under the breaker rating
    2. An individual branch circuit for the EV outlet
    3. A shared circuit, if the outlet has GFCI protection
    4. A shared circuit, unless the charger is rated above 50 A
    Show answer

    Answer: B. Section 625.40 requires an individual branch circuit for an outlet supplying EV equipment rated above 16 A or 120 V. The exception for shared circuits covers multiple EV units under controls allowed by 625.42, which does not fit an air compressor.

    Source: 2023 NEC 625.40, as shown in NFPA's public input report for the 2026 cycle, Panel 12

Practise all 892 questions

What you get with VirtuePrep Journeyman Electrician prep

  • 892 practice questions built around the topics the Journeyman Electrician tests.
  • An explanation for every answer, so each mistake teaches you something.
  • Stats and history that show your weakest topics first.
  • Web, iPhone and Android, so you can study wherever you have ten minutes.

Journeyman Electrician practice test questions people ask

How many questions are on the journeyman electrician test?
It depends on your state or exam. The official bulletins checked on November 7, 2026 ranged from 70 scored questions in Virginia to 100 for the NASCLA exam and California's General Electrician exam. Some exams add non-scored pilot questions on top, so read your own bulletin.
Is the journeyman electrician test open book?
In the bulletins checked, a code book is available, but the rules differ. Texas and Virginia have you bring your own NEC, Minnesota and Colorado supply it, and California supplies references on screen and bans your own materials. Iowa and NASCLA allow the NEC Handbook, while Texas and Oklahoma do not.
Is the journeyman electrician test hard?
That depends on the exam, because each one is different. Time per question is a fair way to compare: Texas gives 110 minutes for its 24 scored calculation questions, while Virginia gives 210 minutes for 70 questions. Texas publishes exam statistics if you want official results for that state.
How many times can you take the journeyman electrician test?
Your state sets this. Texas allows as many attempts as you need, with a fee each time, and California makes you wait 60 days and pay a new fee. Washington requires a 14 day wait, or 90 days after three failures in a year. NASCLA allows three attempts within its one year eligibility.
How long is the journeyman electrician test?
The bulletins checked ran from 180 minutes in Iowa to 330 minutes in Minnesota. Texas splits its exam into a 130 minute portion and a 110 minute portion, and unused time does not carry over. Check whether your bulletin adds time for non-scored questions.
How much is the journeyman electrician test?
Exam fees in the documents checked ran from $50 in Minnesota to $100 in Virginia and California. Texas charges $78 for both portions, plus a separate $30 license application. California's fee page was last revised in 2019, so confirm that figure before you pay.
How many hours for journeyman electrician?
It varies by state. Texas asks for 7,000 hours under a Texas master electrician to sit the exam and 8,000 for the license. California asks for 8,000 hours for its General Electrician certification, and Washington asks for 8,000 hours plus 96 classroom hours.
How long is a journeyman electrician license good for?
Renewal cycles differ by state. Texas renews every year with 4 hours of continuing education, and Minnesota every 2 years with 16 hours. California and Washington renew every 3 years, California with 32 hours of continuing education and Washington with 24.