EPA 608 practice test: what to expect from the real exam

This free EPA 608 practice test has 20 new questions, five each for Core, Type I, Type II and Type III. They were written for this page and are not real exam questions. The real test, officially Section 608 Technician Certification, has 50 questions for a single type or 100 for Universal. The regulation sets the pass mark at 70 percent on closed-book tests.

The US Environmental Protection Agency (EPA) sets the rules and developed the test bank, under the Clean Air Act and 40 CFR Part 82, Subpart F. You test through an EPA-approved program, which also issues your card. There is no single national vendor, so prices and time limits come from the program you choose. This page is exam study information, not legal advice.

Which EPA 608 certification do you need?

You need certification if your maintenance, service, repair or disposal work could release refrigerant. That includes attaching or removing hoses and gauges, adding or removing refrigerant or components, and cutting refrigerant lines. Painting, rewiring external circuits and replacing pipe insulation do not count. People who only dispose of small appliances, vehicle air conditioners or MVAC-like appliances do not need it, and neither does work with exempt substitutes such as carbon dioxide, nitrogen or water.

Certification Equipment it covers Examples from the rule
Type I Small appliances: charged and sealed at the factory, 5 pounds or less Household refrigerators, room air conditioners, vending machines
Type II Medium-, high- and very high-pressure appliances, except small appliances, motor vehicle air conditioners (MVACs) and MVAC-like appliances R-134a, R-22 and R-410A equipment
Type III Low-pressure appliances R-123 and R-11 equipment
Universal All of the above All of the above

EPA's summary page describes Type II as high or very high pressure, while the regulation adds medium pressure. The table follows the regulation. MVAC-like appliances, such as air conditioning on farm and construction equipment, are a special case: technicians may certify as Type II or under Section 609, and EPA recommends they consider Section 609.

EPA's pages state no age, schooling or experience requirement, and class training is voluntary, though a program could set its own conditions. Apprentices are exempt only while a certified technician closely and continually supervises them, and only if registered with the US Department of Labor's Office of Apprenticeship or a recognized State Apprenticeship Council. That status lasts two years from first registering.

Choose with your next few years of work in mind. Each type covers only its own class of equipment, and a mail-in Type I result can never count toward Universal. Buying refrigerant can matter too: EPA's sales restriction page says individuals may buy only in line with the appliances their certification covers, yet it also says Section 608 technicians can generally buy any type, so ask your wholesaler if you hold a single type. If you expect to work on more than one class of equipment, price the proctored Universal test first.

EPA 608 format and scoring

Type II, III and Universal tests are closed book, proctored and held in a secure setting. You can take Universal at one sitting or build it from separately passed Type I, II and III tests. Programs must send your results, and a card if you pass, within 30 days of the test, or within 30 days of receipt for a mail-in Type I.

The rules checked for this page set no federal time limit. ACCA, one approved program, recommends 30 minutes per section and says it does not regulate timing.

Read the scoring closely. Seventy percent of 25 is 17.5, a score no one can get on a single section. ACCA asks for 18 of 25 on each one and gives no credit for a type section unless you pass Core. Other programs may score differently, so treat 18 of 25 in every section as your target until yours tells you otherwise.

EPA 608 study guide: how to split your time

EPA's Test Topics page gives no percentage weights, and EPA releases the test bank only to approved programs. The closest thing to an official split is the question count in Appendix D: 25 of 100 for each section on a Universal test. The amount of material still differs. The study shares below are a judgment based on how many headings each section has on EPA's Test Topics page, and they are not an EPA figure.

Section Questions on Universal Topic headings What sets it apart Suggested study time
Core 25 10 Ozone science, venting and sales rules, the three Rs, cylinders 35 percent
Type I 25 3 Recovery percentages, dead compressors, access fittings 15 percent
Type II 25 6 Evacuation levels by charge size, major repairs, leak rates 25 percent
Type III 25 7 Absolute pressure targets, water in the tubes, purge units, recharging order 25 percent

Move time toward whichever equipment you have not touched. For a single type, split evenly between Core and that type, and study Core first. Watch the units: mixing up 25 mm Hg absolute on Type III with inches of vacuum on Type II is an easy way to lose a point.

The official sources checked give no study-hours figure. Work one section at a time, then take timed, mixed sets, closed book. Reaching 18 of 25 in each section is a sensible practice goal, though practice scores cannot predict your result. The full VirtuePrep bank has 715 EPA 608 questions, with an explanation for every answer.

Does EPA 608 cover A2L refrigerants? They do not appear on the Test Topics page, which was last updated December 5, 2025. That is a fact about the published outline only, and it says nothing about the test bank.

Exam rules versus the job: 50 pounds and 15 pounds

The Test Topics page covers the Part 82 leak repair rules, which apply to appliances with a full charge of 50 pounds or more of an ozone-depleting refrigerant or a blend containing one. The thresholds are 20 percent for commercial refrigeration, 30 percent for industrial process refrigeration and 10 percent for comfort cooling and other appliances.

A separate rule now applies on the job. Since January 1, 2026, 40 CFR 84.106 has required leak repair on appliances with a full charge of 15 pounds or more of HFCs or substitutes with a global warming potential above 53. It excludes residential and light commercial air conditioning and heat pumps, and appliances holding only an ozone-depleting refrigerant. Keep the two apart: answer a question on the Part 82 rules with the 50-pound figures, and do not apply the 50-pound rule to an HFC system at work.

Test Topics also lists the maximum Clean Air Act penalty but gives no figure. When checked on November 7, 2026, 40 CFR 19.4 showed $124,426 under 42 USC 7413(b) for penalties assessed on or after January 8, 2025, so a study guide may show an older number.

What to do next

  1. Pick your certification and find a program on EPA's approved list. Some are for their own employees only.
  2. Ask that program about its fee, time limit, retakes and section scoring.
  3. Take the free questions on this page to find your weakest section.
  4. After you pass, keep a copy of your proof of certification at your place of business. It has to stay there until three years after you stop working as a technician.
  5. If you lose your card, EPA will not replace it. Start with the program that issued it, then follow EPA's lost card steps if that program has closed. To look up a certification, try the program's own list: programs other than federal ones must publish technicians certified on or after January 1, 2017, and technicians can opt out. The pages checked show no central federal lookup.

20 free EPA 608 practice questions

Answer each one yourself, then open the answer. No account needed. These are study questions, not real exam questions.

  1. A building owner has three old units holding R-12, R-22 and R-134a and asks which refrigerant would do the most harm to the ozone layer if released. How do they rank from highest to lowest ozone depletion potential?

    1. R-22, then R-12, then R-134a
    2. R-12, then R-134a, then R-22
    3. R-12, then R-22, then R-134a
    4. R-134a, then R-22, then R-12
    Show answer

    Answer: C. R-12 is a CFC with an ozone depletion potential of 1. R-22 is an HCFC, a class EPA places between 0.01 and 0.1. R-134a is an HFC, with a value of 0.

    Source: EPA: Test Topics

  2. A contractor's office manager, who holds no Section 608 card, goes to a wholesaler to pick up a cylinder of R-410A for the company's crews. Under the sales restriction, when may the wholesaler sell it to her?

    1. When the company gives written evidence that it employs a certified technician
    2. Never, because the person collecting the cylinder must hold the certification
    3. At any time, because R-410A has an ozone depletion potential of zero
    4. Only when the cylinder holds 2 pounds or less of refrigerant
    Show answer

    Answer: A. The restriction covers non-exempt substitutes such as R-410A as well as ozone-depleting refrigerants. An employer of a certified technician, or the employer's authorized representative, may buy if the employer gives the wholesaler written evidence. The wholesaler has to determine that the person really is an authorized representative.

    Source: EPA: Refrigerant Sales Restriction

  3. A service company cleans recovered R-22 with its own recycling machine, and an acid and moisture check on the result looks fine. The office wants to mark the cylinder as reclaimed. What would the refrigerant need before it could count as reclaimed?

    1. A second pass through the recycling machine, with both passes logged
    2. A repeat acid and moisture check by a different certified technician
    3. Transfer to a DOT-approved yellow and gray cylinder with an identifying label
    4. Reprocessing to every applicable Appendix A specification, verified by the set analysis
    Show answer

    Answer: D. Under 40 CFR 82.152, recycling cleans refrigerant for reuse in the same owner's equipment and does not meet all the reclamation requirements. Reclaiming means reprocessing it to every applicable specification in Appendix A, which is based on AHRI Standard 700-2016, then confirming that with the analysis Appendix A prescribes.

    Source: 40 CFR 82.152 (Cornell LII copy)

  4. After brazing a line set on a repaired split system, a technician wants to pressurize the system to look for leaks. Oxygen, a shop air compressor and dry nitrogen are all on hand. Which setup is correct?

    1. Oxygen through a pressure regulator and relief valve
    2. Dry nitrogen through a pressure regulator and relief valve
    3. Compressed air from the compressor through a moisture trap
    4. Dry nitrogen straight from the cylinder valve, opened slowly
    Show answer

    Answer: B. EPA's topics call for nitrogen over oxygen or compressed air for leak detection. They also call for a pressure regulator and a relief valve, because a nitrogen cylinder holds far more pressure than the system is built for.

    Source: EPA: Test Topics

  5. An R-407C system has had a slow vapor leak over a season and has lost part of its charge. The technician suspects the remaining refrigerant will not behave like the original charge. What best explains this?

    1. The remaining vapor has reacted with the oil and formed a new refrigerant
    2. The remaining charge has absorbed nitrogen from the air around the leak
    3. The components of the blend can leak at different rates, changing the mix
    4. The refrigerant has fallen below the 80 percent level that blends need to stay mixed
    Show answer

    Answer: C. R-407C is a blend. EPA's topics name this as the fractionation problem: components of a blend tend to leak at different rates, so what remains may not match the original composition.

    Source: EPA: Test Topics

  6. A technician holds Type I certification only and is offered four jobs. Which one falls within that certification?

    1. A ductless split system piped and charged on site with 4 pounds
    2. A small walk-in cooler assembled and charged on site with 5 pounds
    3. A packaged rooftop unit with a factory charge of 12 pounds
    4. A factory-sealed vending machine that holds about 1 pound
    Show answer

    Answer: D. A small appliance must be fully manufactured, charged and hermetically sealed at the factory, with 5 pounds or less. The charge size alone does not decide it, so a system charged in the field is outside the definition even at 5 pounds or less.

    Source: 40 CFR 82.152 (Cornell LII copy)

  7. A scrap recycler receives factory-sealed dehumidifiers and under-counter ice makers with no paperwork. Instead of asking the supplier for a signed statement, an employee who holds no Section 608 card wants to recover the remaining refrigerant on site. What does the rule allow?

    1. The employee needs a Type I card first, because recovery opens the refrigerant circuit
    2. The employee may do it without a card, using recovery equipment that meets 82.158 and reaching the small appliance levels
    3. The employee may do it without a card, using any pump, because these units are being scrapped
    4. No recovery or statement is needed, because a final processor only has to keep the supplier's invoice
    Show answer

    Answer: B. Two rules combine here. Under 40 CFR 82.161(a)(1)(vii), people who dispose of small appliances do not need certification. Under 82.155, the final processor must either recover what remains or hold a signed statement or contract, and anyone recovering for disposal must reach the 82.156(b) levels with equipment that meets 82.158. Skipping the card does not mean skipping the equipment or the levels.

    Source: 40 CFR 82.155 (Cornell LII copy)

  8. A recovery container partly filled with R-134a from a small appliance has rested until it is at room temperature. Its gauge reads well above the pressure a temperature-pressure chart shows for R-134a at that temperature. What does this most likely mean?

    1. Air or other noncondensables are in the container
    2. Oil carried over with the refrigerant is raising the pressure
    3. The container holds less than half its rated amount of liquid
    4. The refrigerant is leaking slowly out past the container valve
    Show answer

    Answer: A. A container of one refrigerant at rest should sit close to the chart pressure for its temperature. Gases that do not condense add pressure on top of that. EPA's Type I topics list pressure and temperature as the way to identify refrigerants and detect noncondensables.

    Source: EPA: Test Topics

  9. An older chest freezer's data plate says R-12, but a faded tag hints at a retrofit to R-134a. The freezer has rested, compressor off, at 70 degrees F, and the gauge reads 71 psig. The only recovery cylinder on the truck with room already holds clean R-134a. What should the technician do?

    1. Get a separate recovery cylinder, because R-12 and R-134a read almost the same at that temperature
    2. Recover into the R-134a cylinder, because 71 psig matches the R-134a chart value
    3. Recover into the R-134a cylinder, because recycling can split R-12 and R-134a apart later
    4. Recover into an empty disposable cylinder, because it keeps the charge away from the clean R-134a
    Show answer

    Answer: A. EPA's topics list pressure and temperature as a way to identify refrigerants, and they also warn against mixing refrigerants and refilling disposable cylinders. Here the reading cannot settle the identity. NIST saturation data at 70 degrees F gives 84.8 psia for R-12 and 85.8 psia for R-134a, about 70 and 71 psig, so the charge has to stay out of the R-134a cylinder.

    Source: EPA: Test Topics

  10. A technician has finished repairing a drinking water cooler, using a solderless, piercing-type access fitting on the process line. What should happen to the fitting at the end of service?

    1. Leave it in place with its cap tightened for the next service call
    2. Remove it before the appliance goes back into service
    3. Leave it in place after a soap bubble test shows no leak
    4. Mark its location on the cabinet and record it on the invoice
    Show answer

    Answer: B. EPA's Type I topics say solderless access fittings should come off at the end of service. A fitting left on the line stays a possible leak point.

    Source: EPA: Test Topics

  11. A 120 pound R-22 comfort cooling system goes over its leak rate threshold when refrigerant is added on June 1. No repair is made, and the building closes for renovation. On June 11 the system is evacuated to atmospheric pressure and shut down. On September 8 refrigerant is added to restart it. With no extension, by what date must the leaks be repaired?

    1. July 1, because the 30 days keep running through a shutdown
    2. October 8, because the new charge starts a fresh 30 days
    3. September 28, because 20 of the 30 days are left when the clock restarts
    4. No date, because mothballing ends the duty to repair these leaks
    Show answer

    Answer: C. Evacuating to at least atmospheric pressure and temporarily shutting down meets the 82.152 definition of mothballing. Under 82.157(d)(3), that suspends the 30 day repair period, and the time resumes on the day refrigerant is added. Ten days ran from June 1 to June 11, so 20 remain from September 8. The owner must keep records of both dates.

    Source: 40 CFR 82.157 (Cornell LII copy)

  12. A crew has four jobs on R-22 equipment. Which one counts as major maintenance, service or repair under the rule?

    1. Replacing a drier core, opening about 3 square inches for 10 minutes
    2. Removing a failed evaporator coil and fitting a replacement
    3. Replacing a solenoid valve, opening about 2 square inches for 12 minutes
    4. Adding refrigerant through an existing service port after a minor repair
    Show answer

    Answer: B. Major work means removing a compressor, condenser, evaporator or auxiliary heat exchange coil, or opening more than 4 square inches of flow area for more than 15 minutes. Only the coil job meets either test.

    Source: 40 CFR 82.152 (Cornell LII copy)

  13. An office building's comfort cooling system holds 300 pounds of R-22. After a technician adds refrigerant, the calculated leak rate is 14 percent. Setting aside the retrofit or retire option, what does the leak repair rule require?

    1. No repair, because 14 percent is below the 20 percent threshold
    2. No repair, because 14 percent is below the 30 percent threshold
    3. Repair within 120 days, because comfort cooling is given the longer repair period
    4. Repair within 30 days, because the threshold here is 10 percent
    Show answer

    Answer: D. R-22 is a class II refrigerant and the charge is over 50 pounds, so 40 CFR 82.157 applies. Comfort cooling has a 10 percent threshold, with 30 days to repair from the addition. The 120 day period is for an industrial process shutdown.

    Source: 40 CFR 82.157 (Cornell LII copy)

  14. A technician reaches the required recovery vacuum on an R-22 system, shuts the machine off and waits a few minutes. The system pressure then climbs. What is the best next step?

    1. Open the system, because a small rebound is normal once the machine stops
    2. Break the vacuum with nitrogen, because the reading is no longer reliable
    3. Continue recovery, because refrigerant is probably still coming out of the system
    4. Reset the machine's high-pressure cut-out, because the rise shows it has tripped
    Show answer

    Answer: C. EPA's topics say to wait a few minutes after reaching the recovery vacuum to see if pressure rises. A rise suggests refrigerant is still boiling out of trapped liquid or oil, so the system is not ready to open.

    Source: EPA: Test Topics

  15. The gauge on an R-410A system reads 120 psig. The pressure-temperature table the technician has on hand lists its values in psia. Which value should be looked up in that table?

    1. 105.3 psia
    2. 120.0 psia
    3. 134.7 psia
    4. 149.4 psia
    Show answer

    Answer: C. A gauge reads zero at atmospheric pressure, so absolute pressure is higher than the gauge reading. EPA's Type II topics say to add 14.7 to go from psig to psia, and 120 plus 14.7 is 134.7.

    Source: EPA: Test Topics

  16. An R-123 chiller has a full charge of 800 pounds, and its records show it leaked 1,100 pounds during calendar year 2026. Apart from any repair duties, what does the leak repair rule require of the owner or operator?

    1. A report to EPA by March 1, 2027, describing the leak and repair efforts
    2. A report to EPA within 30 days of the last refrigerant addition in 2026
    3. No report, as long as each leak was repaired within its 30 day period
    4. No report, because this reporting duty covers only commercial refrigeration
    Show answer

    Answer: A. The chiller holds a class II refrigerant, has at least 50 pounds and leaked 137.5 percent of its full charge (1,100 divided by 800). At 125 percent or more in a calendar year, 40 CFR 82.157(j) requires a report to EPA by March 1 of the next year, describing the efforts to find leaks and repair the appliance.

    Source: 40 CFR 82.157 (Cornell LII copy)

  17. A 600 pound R-123 comfort cooling chiller vents its purge to a destruction unit with a verified efficiency of 98 percent. Under the rolling average method, 90 pounds were added in the past 365 days, and records show 36 of those pounds replaced refrigerant that was purged and destroyed. The site has never used this exclusion before. What follows?

    1. Repair within 30 days, because 90 of 600 pounds is a 15 percent leak rate
    2. No repair duty at 9 percent, but EPA must be notified within 60 days of first using the exclusion
    3. No repair duty at 9 percent, and site records alone are enough, with no notice to EPA
    4. Repair within 30 days, because the purge exclusion applies only to industrial process refrigeration
    Show answer

    Answer: B. Under 40 CFR 82.157(k), purged refrigerant destroyed at a verifiable 98 percent or better does not count toward the leak rate. That leaves 54 of 600 pounds, or 9 percent, under the 10 percent comfort cooling threshold. The exclusion has its own duties: records under (l)(9) and, under (m)(5), notice to EPA within 60 days after a facility first uses it.

    Source: 40 CFR 82.157 (Cornell LII copy)

  18. An R-123 chiller's evaporator has a tube leak that cannot be isolated from the charge, and pulling the shell to the normal recovery level would draw water into the refrigerant. The evaporator is coming out for replacement. How should the evacuation be handled?

    1. Remove the tube water, then go to the lowest level that avoids substantial contamination, no higher than 0 psig
    2. Keep the water circulating and go to 25 mm Hg absolute, because a major repair has no leak exception
    3. Remove the tube water and stop at 0 psig, because a leaking appliance need not go any lower
    4. Keep the water circulating and stop at 5 psig, because a leaking appliance gets the oil change limit
    Show answer

    Answer: A. Under 40 CFR 82.156(a)(2), when leaks would substantially contaminate the recovered refrigerant, a leaking component goes to the lowest level reachable without that contamination, and 0 psig is the ceiling, not the target. EPA's Type III topics say to circulate or remove chiller water during evacuation to prevent freezing. With a leaking tube, circulating would keep feeding water to the leak, so removal is the choice that fits both.

    Source: 40 CFR 82.156 (Cornell LII copy)

  19. An R-123 chiller is below atmospheric pressure, and a technician needs to bring it up to 0 psig before opening it for a non-major repair. Which method may be used?

    1. Nitrogen up to 0 psig, then purge it out through the purge unit
    2. Compressed air through a regulator up to 0 psig
    3. R-22 vapor up to 0 psig, then recover it before opening
    4. Controlled hot water or the chiller's built-in heating device
    Show answer

    Answer: D. EPA's Type III topics list controlled hot water and a system heating or pressurization device as the allowed methods. R-123 boils below 85 degrees F at atmospheric pressure, so 40 CFR 82.156(a)(1)(ii) bars methods such as nitrogen that need purging afterward. Keep this apart from leak testing, where EPA's topics list nitrogen as the second choice.

    Source: 40 CFR 82.156 (Cornell LII copy)

  20. A low-pressure comfort cooling chiller holds 300 pounds of R-245fa, an HFC, and no other refrigerant. Its calculated leak rate is 16 percent, its compressor is coming out, and the leak will not stop recovery from reaching the normal level. Looking only at 40 CFR 82.156 and 82.157, what applies?

    1. Leak repair within 30 days under 82.157, and evacuation to 25 mm Hg absolute before opening
    2. Leak repair within 30 days under 82.157, with no set evacuation level for a non-ozone-depleting refrigerant
    3. No duty under either section, because neither one reaches a chiller holding only an HFC
    4. No leak repair duty under 82.157, but evacuation to 25 mm Hg absolute before opening
    Show answer

    Answer: D. Since April 10, 2020, 82.157(a) has excluded appliances containing solely substitute refrigerants. Section 82.156 still covers non-exempt substitutes, 82.152 names R-245fa as a low-pressure example, and removing a compressor is major work, so Table 1 sets 25 mm Hg absolute. On the job, also check 40 CFR 84.106, a separate HFC leak repair rule.

    Source: 40 CFR 82.156 (Cornell LII copy)

Practise all 715 questions

What you get with VirtuePrep EPA 608 prep

  • 715 practice questions built around the topics the EPA 608 tests.
  • An explanation for every answer, so each mistake teaches you something.
  • Stats and history that show your weakest topics first.
  • Web, iPhone and Android, so you can study wherever you have ten minutes.

EPA 608 practice test questions people ask

How many questions are on the EPA 608 test?
A Type I, Type II or Type III test has 50 questions: 25 Core plus 25 on that type. A Universal test has 100: 25 Core plus 25 for each of the three types.
What is the EPA 608 passing score?
The regulation sets 70 percent for closed-book Type I, II, III and Universal tests, and 84 percent for a mail-in Type I test. It does not say whether Universal is scored section by section, so ask your program how it scores.
Is the EPA 608 open book?
Type II, Type III and Universal must be closed book and proctored. Only Type I can be taken by mail. A mail-in Type I result or an open-book Core test cannot count toward Universal, so check the format before you pay.
Does EPA 608 expire?
No. EPA says Section 608 credentials do not expire, so there is no renewal. The regulation does let EPA require recertification in the future by Federal Register notice, and a technician whose certificate is revoked must recertify before working again.
How long is the EPA 608 test?
The rules checked for this page set no federal time limit, so the program you choose decides. ACCA, one approved program, recommends 30 minutes per section and says it does not regulate timing. Ask your program before you book.
How hard is the EPA 608 test?
The EPA pages checked give no difficulty rating or pass rate, so this page offers none. The demanding part is recall: Type II, Type III and Universal are closed book, and the evacuation levels, leak rates and recovery percentages change with the equipment. Reaching 18 of 25 in each practice section, closed book, is a fair way to test yourself.
Can you take the EPA 608 online?
Yes, through some programs. EPA's list of approved programs labels entries as remote testing available, online testing only or on-site testing only.
How much does EPA 608 certification cost?
EPA sets no price, and programs may charge reasonable fees. As one example, ACCA's page listed $32.95 per exam plus shipping for its registered proctors on November 7, 2026. Confirm the current price with your program.
What is the difference between EPA 608 and 609?
Section 608 covers stationary refrigeration and air conditioning, and Section 609 covers motor vehicle air conditioning. Training is voluntary for 608, while 609 requires an approved training program before its test. A 609 technician cannot buy refrigerant meant for stationary equipment.